Problems
can be avoided by the selection of optimum processes for the treatment
of water for the fresh water supply and boiler supply water. The basis
for the correct design of such systems is specified by standards and
guidelines such as VDI 2035 and the specifications of the VdTÜV and TRD. In
combination with water analyses, the boiler data and the operating
conditions or water samples and the local conditions on site, JUDO
produces computer-assisted designs, backed up by expert advice and
comprehensive quotations, ensuring that your boiler systems function
perfectly.
JUDO offers you more: Free water analyses + computer-assisted design + selection of the optimum processes + comprehensive quotations and advice + ongoing consultation on site + commissioning and maintenance by our nationwide customer service network = customer care that creates confidence
Data and analysis values for computer-assisted design
Warm water boilers up to 100 °C supply temperature
» Total boiler output (kW) » Heating capacity (m³) » Supply temperature (°C) » Carbonate hardness or acid capacity KS 4,3 (°dH/mmol/l)
Hot water boilers over 100 °C supply temperature
» Total boiler output (kW) » Heating capacity (m³) » Supply temperature (°C) » Complete water analysis (see following table) » Low-salt or high-salt operation
Steam generators
» Total boiler output (kW) » Steam quantity (kg) » Steam pressure (bar) » Condensate return (%) » Complete water analysis (see following table)
Water constituents
Unit
Info
1. pH-level
-
Need
2. Temperature
°C
-
3. Conductivity
µS/cm
Desired
4. Total salt content
mg/l
Desired
5. Iron (Fe++)
mg/l
Desired
6. Manganese (Mn++)
mg/l
Desired
7. Calcium (Ca++)
mg/l
Need (alternative 9)
8. Magnesium (Mg++)
mg/l
Need (alternative 9)
9. Total earth alkalis or total hardness
mmol/l °dH
Need (alternative 7+8)
10. Acid capacity KS 4,3 or carbonate hardness
mmol/l °dKH
Need
11. Sodium (Na+)
mg/l
-
12. Potassium (K+)
mg/l
-
13. Sulfate (SO4--)
mg/l
Desired
14. Chlorine (Cl-)
mg/l
Need
Parameter
Unit
with salt
low-salt
Conductivity
µS/cm
>100 - 1500
10 - 30
>30 - 100
pH-level
-
9 - 10,5
9 - 10
9 - 10,5
Oxygen
mg/l
<0,02
<0,1
<0,1
Earth alkalis
mmol/l
<0,02
<0,02
<0,02
Total hardness
°dH
<0,1
<0,1
<10
Phosphate (PO4)
mg/l
<15
<5
<10
Oxygen bonding agent:
Hydrazine*
mg/l
0,3 - 3
0,3 - 3
0,3 - 3
Sodium sulphite
mg/l
<10
-
-
* only for heating systems without direct drinking water heating
Just give us a call, we are always here for you!
This page shows you pictures of your JUDO contacts.
Please give us a call or send us an e-mail – we will offer you an
optimum solution both from a technical and economic point of view...
Would you like a non-binding quotation on a solution for your specific problem?
Please use the following questionnaire, and fill it out completely. We
also require a current water analysis from you, or you can send us a
water sample taken on site.